How can an MOV start a fire?

Read Note 35

Transcript

How do you protect something plugged into the wall from a lightning surge?

With this disc, a MOV.

Pick the wrong one, and it can start a fire.

It sits across hot and neutral, right after the fuse.

At normal line voltage, it's almost an open circuit.

When a surge hits, it conducts hard and holds the voltage down.

Inside is a disc of zinc oxide grains, pressed and fired like a ceramic.

Every boundary between two grains acts like a tiny switch that turns on at about 3 volts.

A 150-volt part stacks about 80 of them in a row.

Thicker disc, higher voltage. Bigger disc, more current.

I simulated a 2 kV test surge. It carries about 770 amps and holds the line near 420 volts.

That's more than twice the line's 170-volt peak. Everything after it has to take that.

Lightning is the famous cause.

But in a 1960s GE survey, the repeat offenders were inside the house: oil burners, pumps, fridges.

Does every power supply need one? No.

Its big input capacitor already soaks up a 1 kV hit, rising from 170 to 300 volts.

This 30-watt reference design from Power Integrations passes that test with no MOV at all.

At 2 kV, the capacitor passes its 400-volt rating. At 4 kV, it hits 710.

With a MOV, it stays at 350. That's where the MOV earns its place.

Street lights and appliance safety circuits get tested at 2 kV and up.

It wears out, but not the way the joule rating suggests.

A 20 mm part is rated for 120,000 hits at 100 amps, and only 20,000 at 180.

Small hits barely touch it. Big ones use it up fast.

MOVs fail two ways.

A surge too big for it cracks the disc or punches through it, and it fails short.

That one's easy. The fuse right before it blows, and the device goes dark.

The second way starts fires: a stuck overvoltage.

Your house gets 120 volts on each of two legs, sharing one neutral.

If the neutral breaks, the 240 splits unevenly. One side can sit at 180 volts.

The MOV starts conducting on every half cycle. The hotter it gets, the more it conducts.

In a NIST model, 4 extra volts took a 130-volt part from a 130-degree rise to nearly 300.

I simulated two MOVs at 180 volts: a 150-volt part, and a 130-volt part picked for its lower clamp.

The 150 warms 5 degrees. The 130 passes 300 degrees in 43 seconds, drawing a seventh of an amp.

No fuse or breaker sees that. Its lower clamp voltage made it worse.

In a 2024 forensic case, a tree broke the neutral. A power strip's MOV started the fire, with a working 20-amp breaker upstream.

The fix is to pull the MOV out of the circuit before it gets that hot.

Most do it with a thermal fuse built into the part.

A solder wire sits against the disc. At about 180 °C, it melts, balls up, and pulls away.

Hot glue flows in and fills the gap. In my sim, it opens 18 seconds in.

It's one shot. The MOV is gone, and your device keeps running with no surge protection.

That's why some have a third lead, just to report it.

The other way is a PTC, a resistor that jumps in value when it gets hot.

It sits against the MOV, in line with the power. When the MOV heats, the PTC trips and cuts the power.

In TE's lost-neutral test at 400 volts, a plain MOV hit fire temperatures in seconds. Theirs stayed under 150 degrees.

It resets once it cools. But all the power runs through it, so it only fits small loads.

Standards know this. UL tests surge strips at as little as an eighth of an amp, for up to 7 hours.

Oddly, no product standard makes you fit a MOV. Fit one, and it counts as a fire source you have to test.

The right MOV clamps the surge, and drops out before it can start a fire.